Chapter 2 Rack Cabling References
24
10-amp PDU may not provide sufficient receptacles. In this case, use
the Y-cable to connect HP Rack Storage/12 or Rack Storage/12FC
units to the PDUs.
(b) When required, a pair of Y-cables are supplied per pair of Rack
Storage/12 or Rack Storage/12FC units. That is, two Y-cables are
supplied for two units.
(c) Each Y cable connects either the two right power receptacles or the
two left power receptacles of a pair of HP Rack Storage/12 or Rack
Storage/12FC units to one receptacle on the PDU.
Table 2-5. Receptacles Needed for Units
Component Receptacles Required
HP NetServer LH 3000r one
1
for each set of two
power supplies, a second
1
when the optional redundant
power supply is installed
HP Rack Storage/12 two C13 or use Y-Cable
2
All other devices one C13
1. For 110/120 VAC, NEMA 5-15 R, for 200/240 VAC, C13
2. Two Y-Cables may be used to connect two Rack Storage/12 units to
two C13 receptacles.
Power and Current for Estimating Supply Needs
When plugging devices into a PDU and UPS, do not exceed the current capacity
of the PDU nor the power output UPS. Tables 2-6 and 2-7 show the current
requirements of the common rack mounted devices.
Rack configuration utilities available from HP can help you plan the layout of
your rack. Full parts lists as well as diagrams of component positions and details
of power ratings are available. Refer to these if they are available. (See "Rack
Configuration Tools" in this chapter.)