HP 40C Guide de démarrage rapide

Naviguer en ligne ou télécharger Guide de démarrage rapide pour Non HP 40C. HP 40c Getting Started Guide Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer

Résumé du contenu

Page 1

HP Performance Optimized Datacenter 40c G2 Site Preparation and Requirements Guide Abstract This document provides site preparation guidance for the

Page 2

Site requirements 10 Top view clearances shown Side view clearances shown Adequate space around the HP POD 40c G2 is necessary for airflow and co

Page 3 - Contents

Site requirements 11 Verify the following clearances prior to delivery: • Working distance clearance—Maintain a safe working clearance according to

Page 4 - Contents 4

Site requirements 12 Grounding feature Specification Grounding electrode conductor pad • The grounding electrode conductor connection bus pad is

Page 5 - Overview

Site requirements 13 Requirement Specification Connection 1.9 cm (.75 in) G Adapter to 1.9 cm (.75 in) FPS Hardness No greater than 40°fH (equal t

Page 6 - Site safety and security

Site requirements 14 IMPORTANT: The chilled water system piping and heat exchangers must be drained completely, and then purged using compressed a

Page 7 - HP POD 40c G2 capacities

Site requirements 15 Piping materials Do not use the following interconnecting piping materials in a closed water system: • Oxidizing biocides • A

Page 8 - Site requirements

Site requirements 16 A 1N electrical configuration can be achieved by providing all required electrical feeders from a common power source and from

Page 9 - End 1 view clearances shown

Supported facility connections 17 Supported facility connections Environmental control system The ECS developed for the HP water-cooled POD is a sta

Page 10 - Safety and clearance area

Supported facility connections 18 Top view shown Connection portal diameter Connection point Quantity 10.16 cm (4 in) portal Main electrical powe

Page 11 - Grounding requirements

Supported facility connections 19 End view shown You must make the connections between the facility and the HP POD 40c G2. For configuration and in

Page 12 - Utilities

© Copyright 2012 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice. The only warranties

Page 13 - Chilled water supply

Supported facility connections 20 Humidifier A dedicated water supply and approved drainage is required for the humidifier. For more information abo

Page 14

Supported facility connections 21 It is your responsibility to facilitate these connections. HP can make these connections when specifically contrac

Page 15 - Site electrical system

Environmental considerations 22 Environmental considerations Environmental risks • Avoid placing the HP POD 40c G2 directly along a drainage path o

Page 16 - Site requirements 16

Site plan requirements and actions 23 Site plan requirements and actions Completing a site assessment HP requires a detailed site assessment prior t

Page 17 - Environmental control system

Site plan requirements and actions 24 • Ensure that the site safety and security programs are properly administered. • Interface directly with the

Page 18 - Demarcation box

Site plan requirements and actions 25 • Assembly equipment locations HP POD 40c G2 lifting requirements WARNING: The only approved method for

Page 19 - Fire box

Site plan requirements and actions 26 • Access landings might be required to maintain the required access to the HP POD 40c G2 electrical panels.

Page 20 - HP POD 40c G2 security

Appendix A: HP site assessment 27 Appendix A: HP site assessment HP POD 40c G2 site assessment checklist During a survey of the readiness of a propo

Page 21

Appendix A: HP site assessment 28 Item Description Sign-off 8. Clearances Inspect the proposed installation site to confirm clearance requirements

Page 22 - Environmental considerations

Appendix A: HP site assessment 29 Item Description Sign-off 13. Chilled water infrastructure Determine the overall chilled water capacity, availab

Page 23 - Project coordination

Contents 3 Contents Overview ...

Page 24 - Site planning

Appendix A: HP site assessment 30 Item Description Sign-off 9. Permission for Photographs Grant HP permission to take photographs for report illus

Page 25 - Additional structures

Appendix B: Preparing for delivery 31 Appendix B: Preparing for delivery Pre-delivery tasks Allow adequate time for planning, scheduling, obtaining

Page 26

Appendix B: Preparing for delivery 32 Item Description Sign-off 7 When installing on an elevated surface, verify that the maximum height requireme

Page 27

Appendix B: Preparing for delivery 33 Item Description Sign-off 28 Verify the location of the EPO system external to the powerhouses, if applicabl

Page 28 - Item Description Sign-off

Appendix B: Preparing for delivery 34 Item Description Sign-off 3 Verify that the HP Project Team coordinates with other site construction activit

Page 29 - Customer responsibilities

Appendix C: Regulatory compliance notices 35 Appendix C: Regulatory compliance notices HP POD 40c G2 regulatory compliance The HP POD 40c G2 complie

Page 30

Appendix C: Regulatory compliance notices 36 Cables Connections to this device must be made with shielded cables with metallic RFI/EMI connector hoo

Page 31 - Pre-delivery tasks

Glossary 37 Glossary AHJ authority having jurisdiction APJ Asia Pacific Japan BMS building management system door A hinged portion of an enclosur

Page 32

Glossary 38 labeled Equipment or materials to which has been attached a label, symbol, or other identifying mark of an organization that is acceptab

Page 33

Documentation feedback 39 Documentation feedback HP is committed to providing documentation that meets your needs. To help us improve the documentat

Page 34

Contents 4 Completing a site assessment ...

Page 35 - Modifications

Index 40 A about this guide 5 areas prone to lightning or power surges 22 assembly 31 assembly area 24 C cables, FCC compliance 36 Canadia

Page 36

Index 41 R regulatory compliance identification numbers 35 regulatory compliance, HP POD 40c G2 35 S safety information 6, 10 security 6, 20

Page 37 - Glossary

Overview 5 Overview About this document This document outlines the site preparation requirements for an HP Performance Optimized Datacenter 40c G2.

Page 38 - Glossary 38

Overview 6 Site assessment HP requires a detailed site assessment prior to planning and preparing the customer site location for the HP POD 40c G2.

Page 39 - Documentation feedback

HP POD 40c G2 capacities 7 HP POD 40c G2 capacities HP POD 40c G2 capacity limitations The capacity limitations for the HP POD 40c G2 are separated

Page 40 - Index 40

Site requirements 8 Site requirements Site pad The structural design of the HP POD 40c G2 site pad must be based on the specific weight load of the

Page 41 - Index 41

Site requirements 9 End 1 view clearances shown Top view keep-out clearances shown (shaded areas indicate required clearances)

Commentaires sur ces manuels

Pas de commentaire