HP Modular Cooling System Guide de démarrage rapide Page 19

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 93
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 18
Overview 19
Parameter Value Comments
Power cord
230 V, 16 A
208 V, 18 A
IEC 309-to-Procon 700105
NEMA L6-20-to-Procon 700105
The following table lists the electrical specifications for the MCS-200 unit.
Parameter Value Comments
Operating voltage
230 VAC +/- 10%, 50 Hz,
277 VAC +/- 10%, 60 Hz,
and 208 VAC +/- 10%, 60 Hz
AC line phase
Single
Maximum input current
18 A Per line cord
Maximum inrush current
200 A Per line cord
Dropout/hold-up time at
minimum line voltage
20 ms
Transfer time of AC transfer
switch
2 s
Circuit breaker rating
LAHJ Per cord
Power factor
> 0.95 At all loads
Ground leakage current
< 19.4 mA Per line cord
Power cords
230 V, 16 A
208 V, 18 A
IEC 309-to-Procon 700105 (Qty 2)
NEMA L6-20-to-Procon 700105
Vue de la page 18
1 2 ... 14 15 16 17 18 19 20 21 22 23 24 ... 92 93

Commentaires sur ces manuels