Vue de la page 109
0038a
1
1
Figure 54 Rack-mounted 252638–001 PDM
1. PDM mounting brackets, right-side orientation.
Rack AC power distribution
The power distribution in an Enterprise Virtual Array rack is the same for all variants. The site AC input
voltage is routed to the dual PDU assembly mounted in the rack lower rear. Each PDU distributes AC to a
maximum of four PDMs mounted on the left and right vertical rails (see Figure 55).
PDMs 1 th
rough 4 connect to receptacles A through D on PDU 1. Grey power cords connect
these PDMs to the number 1 drive enclosure p ower supp lies and to the upper controller enclosure.
PDMs 5 through 8 connect to receptacles A through D on PDU 2. Black power cords connect
these P
DMs to the number 2 drive enclosure power supplies and to the lower controller enclosure.
NOTE:
ThelocationsofthePDUsandthePDMsarethesameinallracks.