Web interface 16
Solution:
1. Verify the water inlet temperature.
2. Verify that the flow matches the specifications required for heat load.
3. Adjust the temperature assigned in the web interface Intake Temp tab High Temperature Threshold
field.
Leakage detected
Indicators Meaning
Actual operator display alarm
message
Leakage Detected
Actual web interface alarm
message
Leakage Detected
Condition Leak is detected
Modules or sensors Leakage detector actuated
SNMP notification Critical
Type of message Alarm
Solution:
1. Open the rack doors.
2. Power down the rack-mounted components.
3. Turn off the water to the MCS unit.
4. Locate the leak and correct it.
Communication failure
Indicators Meaning
Actual operator display alarm
message
Comm. Failure I²C
Actual web interface alarm
message
Comm. Failure I²C
Condition Management module cannot communicate with the MCS unit sensors
Modules or sensors Any module or sensor
SNMP notification Critical
Type of message Alarm
Solution:
Power cycle the management module. If the alarm message continues to display, replace the management
module with a CSR part. For more information on CSR parts, see "Replaceable parts and maintenance
and service information (on page 55)."
Temperature below threshold (Low Temperature Threshold field)
Indicators Meaning
Actual operator display alarm
message
Temperature Too low