Cooling performance parameter settings 46
IMPORTANT: Temperature Control Manual mode is for service and troubleshooting only and is
not to be used in a production environment.
Parameter Function
Temperature
Control
Used in Auto mode to determine if the MCS unit operates
in Auto mode or Manual mode
Fan Speed Target Used in Manual mode to increase or decrease the fan
speed
Water Valve Used in Manual mode to close or open the water valve
in Manual mode
Flow Meter Model
Used in Auto mode to select the water flow meter that is
installed in the MCS
Minimum Fan
Speed
Used in Auto mode to set the lowest fan speed in Auto
mode
Delta Temperature
for Minimum Fan
Speed
Used in Auto mode to set the maximum delta
temperature when the Minimum Fan Speed will be used
Delta Temperature
for 100% Fan
Speed
Used in Auto mode to set the minimum delta temperature
when the 100% Fan Speed will be used
Cooling Liquid
Heat Capacity
(Cw) Value
Used in Auto mode to calculate the energy extracted by
the air to water heat exchanger unit (This value for pure
water is 4,187 Ws/kg and can be a lower value if
additives are included in the water.)
Delta temperature (Server Intake Temp/Server Exhaust Temp)
Delta temperature is calculated from the temperature difference between the server intake temperature
and server exhaust temperature. The server intake temperature, or cold air, is the air coming from the heat
exchanger units and pushed through the fan units. The server exhaust temperature, or hot air, is the air
coming from the fan units and being pushed through the heat exchanger units.