Web interface 39
Click Restore Configuration to restore the configuration file.
Click Undo Changes to undo the changes.
You can save the configuration and then restore the same configuration on multiple management
modules. The IP address must be set individually on each unit through DHCP or the serial interface before
the replication can be performed.
To replicate a configuration to multiple MCS units, save the configuration file:
1. Configure the settings through the web interface.
2. From the Setup tab (on page 23), select Configuration Save/Restore.
3. Click Save Configuration. Browse to where you want to save the configuration file.
To restore the saved configuration file:
NOTE: Restore only configuration files that have been saved from a MCS unit.
1. At the new unit where you want to restore the configuration file, set the IP address through the serial
interface.
-or-
If the IP address is DHCP assigned, the IP address is available from the operator display.
2. Log in to the web interface.
3. From the Setup tab (on page 23), select Configuration Save/Restore.
4. Browse to where you saved the configuration file.
5. Click Restore Configuration. You are prompted to restart the management module. Do not restart
until you verify or change the network settings.
6. Select to enable or disable DHCP (enabled is the default setting) from the DHCP radio buttons.
7. Set a static IP. For more information, see "Network menu (on page 33)."
8. Reboot the management module.
Help tab
Menu options listed under the Help tab include:
Contents menu (on page 40)
Overview page (on page 41)
Index menu (on page 42)