Adding a Power Supply
Before unpacking the new power supply, inspect the shipping carton for
obvious damage. If damage to the shipping carton is observed, report it to
the carrier immediately.
Carefully unpack the new power supply. Check it for damage. If no
damage is observed, proceed with the instructions that follow. If damage
is noticed, do not install the power supply. Get a replacement power
supply.
WARNING Be careful lifting the power supply into the SPU, it
weights approximately 7.88 Kg (17.5lbs.).
WARNING The AC power to the SPU does not have to be
disconnected to add a power supply to the SPU. Also
the power switch on the SPU does not have to be in
the standby position to perform this task.
To add a power supply in the SPU, perform the following steps:
1. Be sure the power switch on the power supply is in the OFF position.
2. Remove the front bezel.
3. Remove the EMI shield.
4. Remove the power supply slot cover in the desired position, by
loosening the two captive screws at the top edge of the cover, then pull
it away from the SPU.
5. Align the power supply with the selected empty slot in the front of the
SPU.
6. Slide the power supply into the SPU while holding the
insertion/extractor lever out (horizontal).