Table 45 10000 -Series Enterprise 42U Rack Shipping Dimensions
Configurations H eight in / mm Width in / mm Depth in / mm
Max Wt
(packaging)
lbs / kg
Enterprise 2C6
D
8 6 . 2 2 / 219 0 3 2 . 0 / 813 4 8 . 0 / 12 2 0 1111 / 5 0 4
Enterprise 2C12D
86.22 / 2190 3 2.0 / 813 48.0 / 1220 1543 / 700
Enterprise 0C6D
86.22 / 2190 3 2.0 / 813 48.0 / 1220 1011 / 459
Enterprise 0C
12D
86.22 / 2190 3 2.0 / 813 48.0 / 1220 1443 / 6 54
Environmental specifications
To ensure optimum product operation, you must maintain the operational environmental specifications
listed in Table 46. The ambient temperature (the enclosure air intake or room temperature) is especially
critical.
Table 46 Environmental operating specifications
Ambient temperature:+10°Cto+35°C(+50°Fto+95°F)withanaveragerateofchangeof1°C/hour
maximum and a step change of 3 °C or less. Maintaining the optimum ambient temperature within the
specified range ensures that the internal operating temperatures support the drive manufacturer’s MTBF
specifications.
Relative humidity: 40% to 60% (noncondensing) with a step change of 10% or less (noncondensing).
Air quality: Not to exceed a maximum of 500,000 particles, 0.5 micron or larger, per cubic foot of air.
Heat dissipation: 12,70 8 BTU s per hour.
When shipping, or placing this product in short term stora ge, HP recommends maintaining the
environmen
tal conditions listed in Table 47.
Tab le 47 Environm ental shipping or short te rm storage s pecifications
Ambient temperature:–40°Cto+66°C(–40°Fto+151°F)
Relative humidity: 10% to 80% (noncondensing)
Altitude:
below 15,240 m (50,000 ft)
Power specifications
Table 48 defines the AC power specifications for the E nterprise Virtual Array PDUs, PDMs, drive enclosure
power supplies, and controller enclosure power supplies.