0.3.en.03 UNR ECOVERABLE condition—Blower failure
A blower has stop
ped. The operational blower now operates at high speed and is a single point of
failure. This c
ondition report remains active until the problem is corrected.
To correct this problem, record all six characters of the condition report, then contact your authorized
service repr esentative.
0.3.en.04 UNRECOVER ABLE condition—Blower internal
A power supply reported an internal blower error that could affect enclosure cooling and cause an
element to fail. HP recommends correcting the problem before the blower fails. This condition report
remains active until the problem is corrected.
To correct this problem, record all six characters of the condition report, then contact your HP authorized
service repr esentative.
0.3.en.05 NONCRITICAL condition—Blower missing
A blower has been removed or is improperly installed. Even though the blower flaps close to maintain
the proper air flow, the reduced cooling capability can cause overheating, causing an element to fail.
This conditi
on report remains active until the problem is corrected.
To correct this problem, record all six characters of the condition report, then contact your HP authorized
service repr esentative.
0.3.en.06 UNRECOVERABLE condition—No blowers installed
NOTE:
IMPORTANT
When this condition exists there will be two error messages.
The first message will be 0.3.en.05 and will identify the first blower.
The second message will be 0.3.en.06 and will identify the second blower.
TheEMUcannotdetectanyinstalledblowers. S hutdown is imminent! The EMU will shut down the
enclosure in seven minutes unless you correct the problem. This condition report remains active until you
correct the problem or the EMU shuts down the power supplies, whichever occurs first.
Complete the following procedure to correct this problem.
1. Record all six characters of the condition report.
2. Use the controller shutdown procedure to shut down the controllers.
3. Contact your authorized service representative.
CAUTION:
An automatic shutdown and possible data corruption may result if the blower is removed before
a replacement is av ailable.
Temperature conditions
The format of a temperature condition report is 0.4.en.ec,where:
• 0.4. is temperature sensor element type
• en. is the two-character temperature sensor element
• ec is the error code
HP StorageWorks 3000/5000 Enterprise Virtual Array user guide (VCS 4.xxx)