Storage s ystem s
hutdo w n and powerup
The storage sys
tem is shut down using HP Command View EVA. The shutdown process performs the
following func
tions in the indicated order:
1. Flushes cache
2. Removes power from the controllers
3. Disables cach
e battery power
4. Removes power from the drive enclosures
5. Disconnects the system from HP Command View EVA
NOTE:
The storage s
ystem may take a long time to complete the necessary cache flush during controller
shutdown whe
n snapshots are being used. The delay may be particularly long if multiple child snapshots
are used, or
if there has been a large amount of write activity to the snapshot source Vdisk.
Shutting down the storage system
To shut the storage system down, perform the following steps:
1. Start HP Command View EVA.
2. Select the appropriate storage system in the Navigation pane.
The Initialize d Storage System Properties window for the selected storage system opens.
3. Click Shut down.
The Shutdown Options window opens.
4. Under Sy s tem Shutdown click Power Down. If you want to delay the initiation of the shutdown, enter
the number of minutes in the Shutdown delay field.
The controllers complete an orderly shutdown and then power off. The disk enclosures then power
off. Wait for the shutdown to complete.
5. Tu rn off the power switch on the rear of each HSV controller.
6. Tu rn off the circuit breakers on both of the EVA rack Power Distribution Units (PDU).
7. If your mana gement server is an SMA and you are not using it to manage other storage a rrays, shut
down the SMA. From the SMA user interface, click Settings > Maintenance > Shutdown.
Powering up the storage system
To power up a storage system, perform the following steps:
1. Verify that each fabric Fibre Channel switch to which the HSV controllers are connected is powered
up and fully booted. The power indicator on each switch should be on.
If you must power up the SAN switches, wait for them to c omplete their power-on boot process
before proceeding. This may take several minutes.
2. If the management server you shut down is an SMA, power it on and wait for it to completely boot.
Verify the SMA is running by logging into it using the web interface.
NOTE:
Before applying power to the rack, ensure that the power switch on each HSV controller
is off.
HP StorageWorks 3000/5000 Enterprise Virtual Array user guide (VCS 4.xxx)
37