HP Air Pressure Base Station 32
c.
Route the air tube to the area below the floor that you want to monitor.
d. Use cable tie wraps to secure the air tube to a support bracket below the floor.
6. Install the short air tube. This tube monitors the reference pressure above the floor.
a. Attach a flag label indicating the negative terminal to the short air tube.
b. Insert the short air tube into the negative terminal on the air pressure base station. The air tube sits
above the floor.
NOTE: HP recommends installing the base station below the floor tile, if possible.
7. Install the air pressure base station near a subfloor access location, so that the long air tube is routed
under the subfloor and the short air tube is above the floor.
o If a support bracket is available, use cable tie wraps to secure the base station to the support
bracket.